Home | » Products | » Dual Fuel Burner | » PDF Series Dual Fuel Burner |
PDF Series Dual Fuel Burner
Our speedily growing enterprise is affianced towards offering a premium quality range of PDF Series Dual Fuel Burner. This burner is manufactured by making use of optimal quality components and contemporary technology by our vendorâs professionals. It is offered to our clients in numerous specifications to accomplish the exact preferences of our clients. Offered burner is utilized in industrial steam and hot water boilers for burning fuels. This PDF Series Dual Fuel Burner is offered at affordable prices to the clients.
Features:
-
Easy maintenance
-
Excellent heating capacity
-
Long-operational life
-
Robust construction
PDF 160
Product specifications
Capacity | Fuel | Regulation |
---|---|---|
3.3-4.3 MW | LPG/ NG/ Biogas | ON/OFF, HIGH/LOW and Modulating |
The P Series burner can operate on gas (NG, LPG, Towns Gas and Biogas), oil (Class D light oil, Class G HFO) or a dual fuel combination and is available in standard outputs from 3.3MW to 18MW.
Key Features:
Available in monoblock design up to P310 or a duoblock design with a floor mounted combustion air fan
Low NOx Head
Electronic micro modulation air fuel ratio control with individual valve servo motors as standard
Variable Speed Drive (VSD) combustion air fan motor
Air inlet silencer (< 85dBA)
Oxygen trim for improved efficiency and reduced emissions
Separate or integrated water level controls for steam boilers
Data Transfer Interface for BMS control
All P series burners are design and manufactured in accordance with EN267 and EN676.
Model PDF |
160/3.7
|
160/4.0
|
160/4.4
|
160/4.8
|
|
Output (nett CV) |
MW
|
3.3
|
3.6
|
3.9
|
4.3
|
Fan Size
|
kW
|
11
|
11
|
11
|
11
|
Pump Motor
(Distillate Fuel)
|
kW
|
1.5
|
1.5
|
1.5
|
3.0
|
Pump Motor
(Residual Fuel)
|
kW
|
1.5
|
1.5
|
1.5
|
1.5
|
Pre-heater
(Residual Fuel only)
|
kW
|
15
|
18
|
18
|
24
|
Electrical Supply
|
V/Hz
|
400/50
|
400/50
|
400/50
|
400/50
|
Oil inlet pressure
|
psi
|
5 to 10
|
5 to 10
|
5 to 10
|
5 to 10
|
Gas inlet pressure
(min/max)
|
mbar
|
140/300
|
140/300
|
140/300
|
140/300
|
Gas train inlet conn.
|
|
PN16 DN80
|
PN16 DN80
|
PN16 DN80
|
PN16 DN80
|
Operation
|
|
Fully Modulating
|
Fully Modulating
|
Fully Modulating
|
Fully Modulating
|
Control Unit
|
|
Autoflame
Mini Mk7
|
Autoflame
Mini Mk7
|
Autoflame
Mini Mk7
|
Autoflame
Mini Mk7
|
Gas Turndown
|
|
up to 7.0
|
up to 7.0
|
up to 7.0
|
up to 7.0
|
Oil Turndown
|
|
up to 4.0
|
up to 4.0
|
up to 4.0
|
up to 4.0
|
Flame Monitor
|
|
UV Sensor
|
UV Sensor
|
UV Sensor
|
UV Sensor
|
Flame tube lengths
|
mm
|
430/610
|
430/610
|
430/610
|
430/610
|
GAS
|
|
|
|
|
|
Noise
|
dBA
|
92
|
92
|
92
|
92
|
NOx
|
mg/kWh
|
140-190
|
140-190
|
140-190
|
140-190
|
OIL
|
|
|
|
|
|
Noise
|
dBA
|
93
|
93
|
93
|
93
|
NOx
|
mg/kWh
|
200-280
|
200-280
|
200-280
|
20-280
|
CO
|
mg/kWh
|
<110
|
<110
|
<110
|
<110
|
- Contact Details
- PRATHAM ENGINEERING SYSTEMS
- AM-20, Swapna Sagar, S. No. 10/3 /D, Benkar Vasti, Near Kailas Jeevan Factory, Dhayri-Narhe Road, Dhayari, Pune - 411041, Maharashtra, India
- Phone : +917259604779
- Mr. Anant Joshi (Proprietor)