| Capacity | Fuel | Regulation |
|---|---|---|
| 8500kw to 10500 kw | Class D light oil, Class G HFO | HIGH/LOW and Modulating |
The PO Series burner can operate oil (Class D light oil, Class G HFO) and available in standard outputs from 3.3MW to 18MW.
The PO Series burner is commonly used on large industrial steam and hot water boilers.
Key Features:
• Available in monoblock design up to P310 or a duoblock design with a floor mounted combustion air fan
• Low NOx Head
• Electronic micro modulation air fuel ratio control with individual valve servo motors as standard
• Variable Speed Drive (VSD) combustion air fan motor
• Air inlet silencer (< 85dBA)
• Oxygen trim for improved efficiency and reduced emissions
• Separate or integrated water level controls for steam boilers
• Data Transfer Interface for BMS control
All P series burners are design and manufactured in accordance with EN267 and EN676.
| Model PO | 400/9.5 | 400/9.9 | 400/10.3 | 400/10.6 | 400/11.0 | 400/11.4 | 400/11.7 |
| Output (nett CV) MW | 8.5 | 8.9 | 9.3 | 9.6 | 9.9 | 10.3 | 10.5 |
| Fan Size Kw | 18.5 | 22 | 22 | 22 | 22 | 22 | 22 |
| Pump Motor | |||||||
| (Distillate Fuel Kw | 4.0 | 4.0 | 4.0 | 5.5 | 5.5 | 5.5 | 5.5 |
| Pump Motor | |||||||
| (Residuel Fuel) Kw | 4.0 | 4.0 | 4.0 | 4.0 | 4.0 | 4.0 | 4.0 |
| Pre-heater | |||||||
| (Residual Fuel Only) Kw | 48 | 48 | 48 | 48 | 48 | 48 | 48 |
| Electrical Supply V/Hz | 400/50 | 400/50 | 400/50 | 400/50 | 400/50 | 400/50 | 400/50 |
| Oil Inlet Pressure psi | 5 to 10 | 5 to 10 | 5 to 10 | 5 to 10 | 5 to 10 | 5 to 10 | 5 to 10 |
| Fuel Pump | T5 | T5 | T5 | T5 | T5 | T5 | T5 |
| Operation | Fully Modulating | Fully Modulating | Fully Modulating | Fully Modulating | Fully Modulating | Fully Modulating | Fully Modulating |
| Control Unit | Autoflame Mini MK 7 | Autoflame Mini MK 7 | Autoflame Mini MK 7 | Autoflame Mini MK 7 | Autoflame Mini MK 7 | Autoflame Mini MK 7 | Autoflame Mini MK 7 |
| Turndown | Upto to 4:1 | Upto to 4:1 | Upto to 4:1 | Upto to 4:1 | Upto to 4:1 | Upto to 4:1 | Upto to 4:1 |
| Flame Monitor | UV Sensor | UV Sensor | UV Sensor | UV Sensor | UV Sensor | UV Sensor | UV Sensor |
| Flame Tube Lengths mm | 430/610 | 430/610 | 430/610 | 430/610 | 430/610 | 430/610 | 430/610 |
| Noise dBA | 96 | 96 | 96 | 96 | 96 | 96 | 96 |
| Nox mg/kWh | 200/280 | 200/280 | 200/280 | 200/280 | 200/280 | 200/280 | 200/280 |
| CO mg/kWh | ‹110 | ‹110 | ‹110 | ‹110 | ‹110 |

Price: Â
शर्त : नया
माप की इकाई : Unit/Units
न्यूनतम आदेश मात्रा : 1
उपयोग : अन्य, इंडस्ट्रियल
मटेरियल : इस्पात
प्रॉडक्ट टाइप : Industrial Heavy Oil Burner
शर्त : नया
माप की इकाई : यूनिट/यूनिट
न्यूनतम आदेश मात्रा : 1
उपयोग : इंडस्ट्रियल
मटेरियल : इस्पात
प्रॉडक्ट टाइप : Heavy Oil Burners
शर्त : नया
माप की इकाई : यूनिट/यूनिट
न्यूनतम आदेश मात्रा : 1
उपयोग : इंडस्ट्रियल
मटेरियल : इस्पात
प्रॉडक्ट टाइप : Diesel Industrial Burner
शर्त : New
माप की इकाई : Unit/Units
न्यूनतम आदेश मात्रा : 1
उपयोग : Industrial
मटेरियल : Mild Steel
प्रॉडक्ट टाइप : PO310 Oil Burners