Home | » Products | » Nuway Gas Burners | » Gas Burner |
Gas Burner
Product Description
NG 75
Capacity - 677 to 2094 kW
This burner is suitable for use on natural gas and LPG (Towns gas and biogas on request) with-• two stage high/low
• or modulating operation.
All N series burners are custom-built and designed for easy maintenance. This range is typically suited for high resistance, hot water and steam boilers.
Key Features:
• Quick and easy installation
• Reliable and trouble free operation
• Industry standard components available
• Most components can be easily accessed allowing for easy maintenance.
Also available:
• Large gas train options
• Electronic Micro Modulating control
• Variable speed drive to reduce power consumption and noise levels.
All N series burners have been design in accordance with EN676 and EN267.
Burner Type | NGN75 | |
Capacity | kW | 677-2094 |
Fan Motor | V/ph/Hz | 380-420/3/50 |
kW | 3.0 | |
Start Current | A/each phase | 35 |
Run Current | A/each phase | 6.6 |
Cable size | mm2 | 1.5 |
Fuse | HRC (A) | 20 |
Control unit | LFL | |
Operation Options | 2 Stage / Mod | |
Flame monitoring | UV Cell | |
Air damper motor | • | |
Max inlet gas pressure | mbar | 300 |
Noise @ 1m | dBA | 87 |
Gross weight | kg | 130 |
Volume | m3 | 0.77 |